[2.6.0] Change log
Added
 - Unit ID for Modbus RTU can be set via Modbus registers
 - Modbus RTU Stopp bits can be set via Modbus registers
 - Modbus RTU Parity can be set via Modbus registers
 - Default gateway can be set via Modbus registers

----------------------------------------------------------------------------------------------

Quick Guide for Firmware Update via LAN

Step 1: Press and hold the RESET button for about 15 seconds until the device restarts and the status LED flashes green.
Step 2: Open a browser and enter the IP address of the EMD3P.
Step 3: Select the file SU100.up and click Upload.
Step 4: Enter the password found on the additional label in the device packaging.
Step 5: If successful, the web interface will display “Update erfolgreich” and the EMD3P will restart automatically. You can then close the page.


Important Note

The correct update file name ends with "SU100.up" e.g. v2.6.0_SU100.up. Using a different name will cause the update to fail.

----------------------------------------------------------------------------------------------

Additions on Modbus Registers:

Start address  End address  Start address  End address  Size  Type    Description          Values
(dec)          (dec)        (hex)          (hex)
271            274          0x010F         0x0112       4     uint16  Default Gateway      Default Gateway for network configuration
280            280          0x0118         0x0118       1     uint16  Modbus RTU Unit ID   Unit ID between 1 and 247
281            281          0x0119         0x0119       1     uint16  Modbus RTU Parity    0 - None
                                                                                           1 - Odd
                                                                                           2 - Even
282            282          0x011A         0x011A       1     uint16  Modbus RTU           Stopp bits
                                                                                           1 - One stopp bit
                                                                                           2 - Two stopp bits

Changes become active after restart. Please refer to Restart Register.
For the ip configuration, each of the four octets must be written into a register.

----------------------------------------------------------------------------------------------